- Maintains the M-2001C energized during power outages to maintain the
continuity of the communications loop
- Accepts power input from station auxilary supply over a range of 105
V ac to 140 V ac (50 or 60 Hz)
- Fuse protected and transient suppressed, input and output
- Substation hardened
-40° C to +85° C
- Conformal coated
Input
- 105 V ac to 140 V ac at 50Hz/60Hz
- Burden of less than 2 VA
- Fuse protection (1.5 A)
- Transient protected
Output
- +12 V dc nominal @ 1 amp
- Fuse protected (1.5 A)
- Transient protected
Transient Protection
- Surge Withstand Capability:
- IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 4000 V pk fast transient
burst
- IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 5000 V pk fast transient
burst