- Maintains the M-2001C energized during power outages to maintain
the
continuity of the communications loop
- Accepts power input from station auxilary supply over a range of
105 V ac
to 140 V ac (50 or 60 Hz) or 105 V dc to 140 V dc
- Fuse protected and transient suppressed, input and output
- Substation hardened -40° C to +85° C
- Conformal coated
Input
- 105 V ac to 140 V ac at 50Hz/60Hz or 105 V dc to 140 V dc
- Burden of less than 8 VA
- Bipolar Fuse protection (1.5 A)
- Reverse polarity protection for a dc input
- Transient protected
Output
- +12 V dc regulated (+/- .5 V) @ 1.5 amp
- Transient protected
Transient Protection
- Surge Withstand Capability:
- IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 4000 V pk fast transient
burst
- IEEE C37.90.0-2002: 2500 V pk-pk oscillatory, 5000 V pk fast transient
burst

Sales and Service
For sales and service information
contact your local representative
or contact the factory:
E-mail: sales@beckwithelectric.com
Call (727) 544-2326
or Fax (727) 546-0121
|
 |
Product Specifications

 |