Impact of Voltage Transformer Connection and Grounding
on Generator Protection Security and Selectivity
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| VT Connection | Relay Connections | 24, 27 and 59 elements are secure for primary phase to ground faults | 59N element is secure for VT secondary phase to ground faults | Can use directional ground elements (zero-sequence polarized) | Can use single phase power elements | Can view discrete phase voltages |
![]() |
Vag, Vbg, Vcg (L-G voltages) |
No
|
No
|
Yes
|
Yes
|
Yes
|
![]() |
Van, Vbn, Vcn (L-N voltages) |
No
|
Yes
|
Yes
|
Yes
|
Yes
|
![]() |
Vab, Vbc, Vca (L-L voltages) Neutral not wired |
Yes
|
Yes
|
No
|
No
|
No
|
![]() |
Vab, Vbc, Vca (L-L voltages) |
Yes
|
Yes
|
No
|
No
|
No
|
![]() |
Vag, Vbg, Vcg (L-G voltages) L-L quantities derived in relay software |
Yes
|
No
|
Yes
|
Yes
|
Yes
|
![]() |
Vab, Vbc, Vca (L-L voltages) |
Yes
|
Yes
|
No
|
No
|
No
|
![]() |
Van, Vbn, Vcn (L-N voltages) L-L quantities derived in relay software |
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|