|
Introduction
Summary
Quiz
Glossary
Online Learning Center
Beckwith Electric Home
|
Impact of Voltage Transformer Connection and Grounding
on Generator Protection Security and Selectivity
Example One: Wye primary / wye secondary, neutral grounded
To source generator protective relaying, several VT arrangements may
be used, based on application and cost considerations.
A) Wye primary / wye secondary, neutral grounded (Figure 1)

Figure 1, Wye Primary / Wye Secondary, Neutral Grounded
Pros:
- This arrangement offers the ability to use single-phase power elements
- This arrangement offers the ability to zero-sequence directionalize
ground elements from phase-to-neutral voltages and employ the 59D element
- This arrangement offers the ability to view discrete phase voltages
on the waveform capture
Cons:
- This arrangement may allow the 24, 27, and 59 elements to operate
for phase to ground faults in the generator zone. This is due to a having
ground fault on an essentially ungrounded system (the generator zone
is high impedance grounded and terminated in the ungrounded delta winding
of the generator step up transformer) causes a neutral shift with attendant
high voltages (approaching VLL) on the unaffected phases, and a near
zero voltage on the affected phase. See Figure
2.

Figure 2, Ground Fault with Neutral Shift and Resultant Voltages on High
Impedance Grounded Generator
(High Impedance Grounded System approximates Ungrounded System)
- This arrangement may allow the ground overvoltage protection (59N)
to operate on VT secondary side ground faults (time coordination dependent).
This is because a phase to ground fault on the secondary side as a phase-to-ground
fault on the primary (See Figure
3).
- This arrangement is typically the most expensive (compared to open
delta), as three VTs are required.
Figure 3, Wye Primary / Wye Secondary, Neutral Grounded Ground Fault
on Secondary Side, Appears as Ground Fault on Primary Side
Page 2 of 9

|