Provides
remote Capacitor Automated Monitoring and Protection (CAMP)
- Fail-safe chargeover to M-2501B Autodaptive® Capacitor Control for
100% hardware backup in the event of communication loss
- The control can integrate any serial communications media
- Direct DNP 3.0 slave for SCADA Level VAr Dispatch program interface
- Neutral unbalance detection to indicate cap bank problem (unsolicited
reporting)
- Provides remote bypass Capacitor Control operation using two-way communications
- Capacitor control commands that can be initiated remotely include
Auto, Open Bank, Close Bank, Counter Reset and Initialize control
- System monitoring includes capacitor bank control status, switching
status, measured voltage setpoint and limits information, as well as
control alarm and capacitor bank report-by-exception failure monitoring
- Accessories include M-2990 Hardware Mounting kit, and M-2941 BecoEye+
Handheld Infarred Field Communications Device for local communications
that include configuration, settings and data download
The M-2980 CAMP™ Remote Capacitor Bank Control provides a remote communications
interface for the M-2501B Autodaptive® Capacitor Control. The M-2980 provides
remote capacitor control, system data monitoring, alarms and failure polling
of remote capacitor banks from an RTU or Scada Master running DNP3.0.
Interface
Physical
The M-2980 includes four female meter blade receptacles in an industry
standard 100 Amp class meter socket to accept the four meter blades from
the M-2501B control. A 5th stab is utilized when the unbalance neutral
detection is required. This meter blade receptacles are located inside
a NEMA 4X rated weatherproof enclosure that houses the wireless device,
as well as power supply and interface circuitry.
Infrared
The IR link from the M-2980 to the M-2501B control consists of an internally
routed optical path. The M-2501B contains an IR port exiting the back
of the control through the mounting base, in addition to the traditional
IR port exiting the bottom of the control through the Lexan™ cover. The
rear IR port communicates with the wireless device using an IR port mounted
to the rear of the enclosure.
Antenna
The M-2980 antennas are matched to the specific wireless device that the
unit is equipped with.
Power
The M-2980 and the attached M-2501B are powered by the VT provided with
the switched capacitor bank. The power supply for the radio can be configured
for either 12 V or 5 V at 10W and is provided with a 2.0 Amp, fast-acting
3 AG type fuse. The M-2501B Capacitor Control possesses an internal fuse
independent of the M-2980.
Neutral Current Unbalance Detection (Optional)
An optional Neutral Current Transformer can be installed around the neutral
lead of the capacitor bank. It is sized to handle any expected imbalanced
currents without saturation. The CT for Neutral Current detection input
allows for the following options:
- 100:5 Amp CT
- 100:1 Amp CT
- 100 Amps to 0.333 V ac
- The CTs can be either split-core or solid-core
- CT can be either wired into the terminal board or to 5th stab of meter
base
Features
The following functions and features can be remotely initiated utilizing
an RTU or SCADA Master running DNP3.0, connected to a two-way radio with
appropriate interface programming:
Perform the following operations using Control Outputs
- Manual Open/Close
- Set Auto/Manual Mode
- Select Variable/Fixed Voltage Setpoint
- Counter Reset
- Reinitialize Control
- Enable/Disable Control Configuration Settings
Write the following using Analog Outputs
- Voltage Setpoint
- Voltage Correction Factor
- Upper and Lower Limits
- Voltage Override Analysis Settings
- Neutral Current Analysis Settings
- Alarm Settings
- DNP Address Settings
Status bits can be read using the binary Inputs
- Capacitor Bank Position
- Control Mode
- Local Switch Position
- Warnings and Alarms
- Enable/Disable Settings
Timers and Counters can be read using Counter Inputs
- Counts per day
- Resettable Operation Counter
- Number of days
- Timer Variable (sec)
- Neutral Current Countdown Time (sec)
- Communication Heartbeat Countdown Timer (sec)
Monitored values can be read using Analog Inputs
- Measured Voltage
- Voltage Max and Min (15 minute average)
- Bandwidth • Neutral Current %
- NC Max and Min (15 minute average)
- Average Voltage (long term)
- Radio Signal Strength Indicator (RSSI)
- RSSI Max and Min (15 minute average)
Communication
The software embedded in the M-2501B control and the M-2980 CAMP module
enable the customer to communicate with a network of controls using an
RTU or SCADA Master running DNP3.0 Disruption Network Protocol.
Accessories
M-2941 BecoEye+
The M-2941 BecoEye+TM Handheld Infrared Field Communications Device communicates
all M-2501/M-2501A/B Autoadaptive® Capacitor Control operational commands,
setting changes and data retrieval functions.
M-2990 Mounting Hardware Kit
The Mounting Hardware Kit includes the necessary hardware to mount the
M-2980 to a pole, up to 14" (35.6 cm) in diameter.

Sales and Service
For sales and service information
contact your local representative
or contact the factory:
E-mail: sales@beckwithelectric.com
Call (727) 544-2326
or Fax (727) 546-0121
|