We offer our most popular configurations; however, if you need a different
configuration, please complete the following questionnaire, click on submit
and we will call you within the next business day with a quote for an
M-3410A including your specific options. Domestic shipments are F.O.B.
factory. International shipments are FCA factory. Prices subject to change
without notice. Prices listed are in USA dollars. All orders are subject
to Beckwith Electric Co., Inc. standard terms of agreement.
DESCRIPTION: The Intertie/Generator Protection System ® M-3410A provides protection, control, monitoring and user interface functions. Includes protection for abnormal voltage, frequency, overcurrent, directional power, and VT fuse loss. Sync-check and programmable reconnect time are also provided. Stored sequence of events and oscillography are included as extended functions. RS-232 and RS-485 communication ports provide user and SCADA interface capabilities. The M-3810A IPScom ® Communications Software is included for direct serial or remote communication access. Waveform data can be downloaded using IPScom, while the IPSplot ® PLUS Oscillograph Analysis Software allows for plotting and printing of the downloaded oscillographic data. Sensing voltage up to 480 volts, accepts 1 A or 5 A nominal current, phase rotation (ABC or ACB) and nominal frequency (50 or 60 Hz) are user selectable in software. |